Impact of Short-Circuit Ratio Change to HVDC Operating Characteristics
Author :
Liu Xiao-jiang ; Yang Hong-Geng ; Zhou Yun-feng
Author_Institution :
Sch. of Electr. Eng. & Inf., Sichuan Univ., Chengdu, China
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
4
Abstract :
The stability of HVDC system is under the influence of the strength of AC system, which is reflected as the AC and DC short-circuit ratio(SCR) on the converter stations. In this paper, a simulation study is carried out on the sending end of a certain HVDC system that has been put into operation under different SCR, using PSCAD/EMTDC. The simulation indicates that with the reduction of SCR, the recovery time and transient overvoltage increase, and in some cases harmonic instability come out. Under the small SCR with harmonic instability, it is found from analysis that harmonic instability will emerge when busbar voltage and line current harmonic contents reach a certain level. The simulation results play an directing role for the prevention and detection of harmonic instability.
Keywords :
EMTP; HVDC power convertors; HVDC power transmission; power system harmonics; power system stability; short-circuit currents; AC short-circuit ratio; DC short-circuit ratio; HVDC operating characteristics; HVDC system stability; PSCAD-EMTDC; busbar voltage; converter stations; harmonic instability; line current harmonic contents; recovery time; transient overvoltage; Circuit faults; Converters; HVDC transmission; Harmonic analysis; Power harmonic filters; Thyristors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
ISSN :
2157-4839
Print_ISBN :
978-1-4244-6253-7
Type :
conf
DOI :
10.1109/APPEEC.2011.5748453
Filename :
5748453
Link To Document :
بازگشت