  • Abstract
    This paper investigates the insulation reliability of 380 kV XLPE cable systems. In order to obtain sufficient service experience of 380 kV XLPE cable systems and detailed failure information, both literature survey and internal interview with several TSO´s (Transmission System Operators) in Europe have been carried out. Based on the collected in-service and failure populations regarding insulation, failure rates of 380 kV XLPE cable systems are statistically investigated with a confidence interval, regarding to some uncertainties. The calculated failure rates are compared with those from literatures. It shows that the results that the failure rates from the existing literatures are not suitable for 380 kV XLPE cable systems, because they are dominated by the failures from 220 kV cable systems. The most important consequence for TSO´s is forced outage time, therefore these outage time caused by failures is also discussed.
  • Keywords
    XLPE insulation; failure analysis; power cable insulation; reliability; TSO; XLPE cable systems; insulation reliability; transmission system operators; voltage 220 kV; voltage 380 kV; Cable insulation; Communication cables; Europe; Maintenance engineering; Power cables; Reliability; EHV XLPE cables; failure rates; reliability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference (EIC), 2011
  • Conference_Location
    Annapolis, MD
  • ISSN
    pending
  • Print_ISBN
    978-1-4577-0278-5
  • Electronic_ISBN
    pending
  • Type

    conf

  • DOI
    10.1109/EIC.2011.5996193
  • Filename
    5996193