DocumentCode :
2928445
Title :
Field implementation of a transient voltage measuring facility using HV current transformers
Author :
Siebrits, FB ; Vermeulen, HJ ; Tlhatlhetji, NP
Author_Institution :
Stellenbosch Univ., South Africa
Volume :
2
fYear :
2002
fDate :
2-4 Oct. 2002
Firstpage :
629
Abstract :
This paper discusses the design and field implementation of a facility for the measurement of wideband high voltage (HV) transient waveforms using a normally earthed substation current transformer (CT) configured in a transconductance voltage measuring topology. This implies that the HV waveforms are obtained by integrating the CT earth currents. The design, implementation and performance evaluation of dedicated instrumentation for the measurement, summation, integration and acquisition of multiple earth currents under field conditions are discussed. It is shown that a system with a measuring bandwidth of the order of 500 kHz can be realized.
Keywords :
current transformers; data acquisition; earthing; electric current measurement; optical cables; substations; transients; voltage measurement; 500 kHz; HV waveforms; earth currents; fibre optic link; multiple earth currents acquisition; normally earthed substation current transformer; performance evaluation; summation; transconductance voltage measuring topology; wideband high voltage transient waveforms; Bandwidth; Current measurement; Current transformers; Earth; Instruments; Substations; Topology; Transconductance; Voltage measurement; Wideband;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Africon Conference in Africa, 2002. IEEE AFRICON. 6th
Print_ISBN :
0-7803-7570-X
Type :
conf
DOI :
10.1109/AFRCON.2002.1159983
Filename :
1159983
Link To Document :
بازگشت