Research on Fast Fault Isolation and Restoration for Distribution
Author :
Ma, Shicong ; Xu, Bingyin ; Deng, Feng ; Bo, Zhiqian
Author_Institution :
Alstom Grid, Stafford, UK
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
4
Abstract :
A new fault isolation and restoration technique for distribution automation, which employs local Ethernet network, is presented. It can isolate all short circuit faults in the loop within 300ms and restore the supply of healthy sections in less than 1.2 seconds. A reliable fault location method for isolating the single phase to ground fault in the non-effectively earthed network, which makes use of the fault generated transient signals is also proposed. The simulation and Laboratory test results show the proposed techniques are reliable and feasible.
Keywords :
power distribution faults; power engineering computing; Ethernet network; distribution automation; fault isolation; fault location method; fault restoration; short circuit faults; transient signals; Automation; Circuit faults; Ethernet networks; Fault diagnosis; Integrated circuit reliability; Switches; Transient analysis;