Abstract :
On ultra-high-voltage (UHV) lines, the existence of secondary arc impact on the stable operation of system, so it is necessary to further study secondary arc. The paper adopts total harmonic distortion (THD) to judge the status of arc. First, the simulation model of secondary arc is established by ATP software. Then, faulted phase voltage and secondary arc are simulated in different close angle. Last, spectrum characteristics and harmonic content of faulted phase are analyzed, at the same time, THD is obtained by Fourier algorithm. The simulation results show that THD of faulted phase voltage decrease as close angle in every fourth cycle, which provide the basis for judging state of arc by using harmonic content of faulted phase voltage. The analysis of spectrum characteristics of harmonic content is certain significance in the design of choosing insulation materials and insulation structure.
Keywords :
Fourier transforms; harmonic distortion; high-voltage techniques; power transmission lines; Fourier algorithm; UHV transmission lines; faulted phase voltage; secondary arc spectrum characteristics; total harmonic distortion; ultra high-voltage lines; Analytical models; Circuit breakers; Circuit faults; Grounding; Harmonic analysis; Power system harmonics; Power transmission lines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
Conference_Location :
Xi´an
Print_ISBN :
978-1-4577-1273-9
Type :
conf
DOI :
10.1109/ICEPE-ST.2011.6122933
Filename :
6122933
Link To Document :
بازگشت