• DocumentCode
    2930325
  • Title

    Feasibility study of metalized membrane method applied to monitoring corona loss of AC/ DC transmission line

  • Author

    Liu, Haicang ; Zhang, Qi ; Luo, Yongfen ; Wu, Jian ; Bai, Xiaochun

  • Author_Institution
    Sch. of Electr. Eng., Xi´´an Jiaotong Univ., Xi´´an, China
  • fYear
    2011
  • fDate
    23-27 Oct. 2011
  • Firstpage
    253
  • Lastpage
    257
  • Abstract
    A new method to measure leakage current of AC and DC corona loss using metalized membrane is presented in this paper. Transmission line is coated by metalized membrane whose is insulated layer next to transmission line and mental layer outwards. The sampling resistance between transmission line and membrane can convert leakage current to voltage signal which will be sent to computer. The voltage of transmission line will also be sent to computer after converting by PT or voltage divider. Corona current and loss can be calculated by program. This method can be applied to on-load or un-load line of AC and DC. It proves that this method is feasible after analyzing correlation coefficient, time delay and corona loss per meter.
  • Keywords
    corona; power transmission lines; AC corona loss monitoring; AC-DC transmission line; DC corona loss monitoring; PT; leakage current; metalized membrane method; time delay; voltage divider; voltage signal; Corona; Leakage current; Loss measurement; Power transmission lines; Propagation losses; Resistance; Transmission line measurements; Corona Loss; Correlation Coefficient; Metalized Membrane Method; Time Delay;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    978-1-4577-1273-9
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2011.6122982
  • Filename
    6122982