Title :
Analysis and Discussion of SF6 Byproducts in Simulated Electric Equipment of Overheating Faults in Low Humidity
Author :
Wang, Yu ; Li, Li ; Yao, Weijian
Author_Institution :
Environ. Protection Dept., Electr. Power Test Res. Inst., Guangzhou, China
Abstract :
The decomposition of sulfur hexafluoride (SF6) in overheated electric equipment at different temperature in low humidity was simulated in the study. SF6 is very stable and not significantly decomposed at 200°C, 250°C and 300°C. SF6 is significantly decomposed at 350°C. SF6 is more easily to be decomposed and decomposed more rapidly at higher temperature.
Keywords :
SF6 insulation; electrical faults; SF6 byproduct; low humidity; overheating fault simulated electric equipment; sulfur hexafluoride decomposition; temperature 200 degC; temperature 250 degC; temperature 300 degC; temperature 350 degC; Hafnium; Heating; Humidity; Impurities; Moisture; Power systems; Sulfur hexafluoride;
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
Print_ISBN :
978-1-4244-6253-7
DOI :
10.1109/APPEEC.2011.5748656