Abstract :
Acetylene always arises from the discharge faults of power transformers. A photoacoustic spectrometer was developed and it has been applied to the detection of acetylene using a properly designed photoacoustic cell on its first longitudinal mode. Experimental results show that the photoacoustic signal has a significant linear correlation with the gas content and the laser power under low gas content or low laser power. The minimum detection limit of acetylene is about 1.43 part-per-million by volume. Moreover, in this paper we also describe some basic theory of gas photo-acoustic spectroscopy.
Keywords :
photoacoustic spectroscopy; power system faults; power transformers; transformer oil; acetylene; discharge fault; gas photoacoustic spectroscopy; linear correlation; photoacoustic cell; photoacoustic detection method; photoacoustic spectrometer; power transformer; transformer oil; Acoustics; Gas lasers; Gases; Oil insulation; Power lasers; Q factor; Semiconductor lasers;