DocumentCode :
2941546
Title :
Analysis of an Isolated Half-Wavelength Transmission Line Submitted to Switching Maneuvers
Author :
Tavares, Maria Cristina ; Borges, Ricardo B. ; Portela, Carlos Medeiros
Author_Institution :
Sch. of Electr. & Comput. Eng., Univ. of Campinas, Campinas, Brazil
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
5
Abstract :
This paper presents some electromagnetic transient results on a Transmission Line a little greater than the Half Wavelength (HWL+). It was used an 800 kV non-conventional line with 2600 km and towers with three bundles of eight conductors each and a natural power of 4.8 GW. The studies conducted consist of line energization, load rejection, line tripping and reclosing. The transients arisen from the maneuvers were less severe than those on lines of some hundreds of kilometers.
Keywords :
conductors (electric); overvoltage protection; poles and towers; power transmission lines; transient response; electromagnetic transient; isolated half-wavelength transmission line; line energization; line reclosing; line tripping; load rejection; power 4.8 GW; size 2600 km; switching maneuvers; voltage 800 kV; Power transmission lines; Resistors; Rivers; Synchronization; Transient analysis; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
ISSN :
2157-4839
Print_ISBN :
978-1-4244-6253-7
Type :
conf
DOI :
10.1109/APPEEC.2011.5749126
Filename :
5749126
Link To Document :
بازگشت