    Analysis of an Isolated Half-Wavelength Transmission Line Submitted to Switching Maneuvers

  • Author

    Tavares, Maria Cristina ; Borges, Ricardo B. ; Portela, Carlos Medeiros

  • Author_Institution
    Sch. of Electr. & Comput. Eng., Univ. of Campinas, Campinas, Brazil
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper presents some electromagnetic transient results on a Transmission Line a little greater than the Half Wavelength (HWL+). It was used an 800 kV non-conventional line with 2600 km and towers with three bundles of eight conductors each and a natural power of 4.8 GW. The studies conducted consist of line energization, load rejection, line tripping and reclosing. The transients arisen from the maneuvers were less severe than those on lines of some hundreds of kilometers.
  • Keywords
    conductors (electric); overvoltage protection; poles and towers; power transmission lines; transient response; electromagnetic transient; isolated half-wavelength transmission line; line energization; line reclosing; line tripping; load rejection; power 4.8 GW; size 2600 km; switching maneuvers; voltage 800 kV; Power transmission lines; Resistors; Rivers; Synchronization; Transient analysis; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5749126
  • Filename