Analysis of an Isolated Half-Wavelength Transmission Line Submitted to Switching Maneuvers
Author
Tavares, Maria Cristina ; Borges, Ricardo B. ; Portela, Carlos Medeiros
Author_Institution
Sch. of Electr. & Comput. Eng., Univ. of Campinas, Campinas, Brazil
fYear
2011
fDate
25-28 March 2011
Firstpage
1
Lastpage
5
Abstract
This paper presents some electromagnetic transient results on a Transmission Line a little greater than the Half Wavelength (HWL+). It was used an 800 kV non-conventional line with 2600 km and towers with three bundles of eight conductors each and a natural power of 4.8 GW. The studies conducted consist of line energization, load rejection, line tripping and reclosing. The transients arisen from the maneuvers were less severe than those on lines of some hundreds of kilometers.
Keywords
conductors (electric); overvoltage protection; poles and towers; power transmission lines; transient response; electromagnetic transient; isolated half-wavelength transmission line; line energization; line reclosing; line tripping; load rejection; power 4.8 GW; size 2600 km; switching maneuvers; voltage 800 kV; Power transmission lines; Resistors; Rivers; Synchronization; Transient analysis; Voltage control;