Comparison of Two Calculation Methods of Flicker Caused by Wind Power
Author
Xiao Hui ; Liu Yong ; Liu Huijing
Author_Institution
Coll. of Electr. Eng., Wuhan Univ., Wuhan, China
fYear
2011
fDate
25-28 March 2011
Firstpage
1
Lastpage
4
Abstract
Wind farm integrated in power system in continuous operation will cause the PCC(Point of Common Coupling) of voltage fluctuation and flicker. The wind changes can contribute to the wind turbine output power fluctuations, which can lead to a connection point of voltage fluctuation and flicker reasons. IEC61400-21 gives the wind turbine on the grid power quality requirements and analyses the flicker calculation method of PCC, while there is another method of flickermeter flicker measurement recommended by IEC/UIC. In response to these two methods to do analysis and comparison of the 110kV bus of some a wind farm of He´nan province, the former method obtained flicker value of PCC is rather small, while the latter more in line with the measured data.
Keywords
fluctuations; power grids; power supply quality; wind power plants; wind turbines; He´nan province; IEC61400-21; continuous operation; flicker calculation; flicker measurement; flickermeter; grid power quality requirements; power system; voltage 110 kV; voltage fluctuation; wind farm; wind power; wind turbine; Band pass filters; Fluctuations; Generators; Low pass filters; Voltage fluctuations; Wind farms; Wind power generation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location
Wuhan
ISSN
2157-4839
Print_ISBN
978-1-4244-6253-7
Type
conf
DOI
10.1109/APPEEC.2011.5749129
Filename
5749129
Link To Document