Title : 
The Effect of OLTC on Static Voltage Stability Limit
         
        
            Author : 
Duan Jundong ; Zhu Shanshan
         
        
            Author_Institution : 
Sch. of Electr. Eng. & Autom., Henan Polytech. Univ., Jiaozuo, China
         
        
        
        
        
        
            Abstract : 
Voltage stability problems caused by on-load Tap Changer (OLTC) action and load dynamic characteristics are more complicated and not easy to grasp. By means of the Pmax - Φ and Vcr - Φ curves, this paper analyses the influence of OLTC on the static voltage stability limit, and studies the critical variable ratio corresponding to the OLTC adjustment. The Pmax - Φ and Vcr - Φ curves gradually shift upward with the continuous increment of transformation ratio n of on-load Tap Changer; the Pmax - Φ and Vcr - Φ curves gradually shift down with the continuous decrease of OLTC transformation ratio n. During the adjustment of OLTC ratio, its range can not exceed the adjustment area determined by the critical variable ratio. Finally the example simulation proves that Pmax - Φ and Vcr - Φ curves can well describe the influence of OLTC adjustment on the static voltage stability limit.
         
        
            Keywords : 
on load tap changers; power system stability; critical variable ratio; load dynamic characteristics; on-load tap changer action; static voltage stability limit; Impedance; Power system dynamics; Power system stability; Stability criteria; Video recording;
         
        
        
        
            Conference_Titel : 
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
         
        
            Conference_Location : 
Wuhan
         
        
        
            Print_ISBN : 
978-1-4244-6253-7
         
        
        
            DOI : 
10.1109/APPEEC.2011.5749167