• DocumentCode
    2949377
  • Title

    Risk of ferroresonance in isolated neutral networks and remedies

  • Author

    Stucken, C. ; Monfils, P.-A. ; Janssen, N. ; Van Craenbroeck, T. ; Van Dommelen, D.

  • Author_Institution
    Laborelec, Belgium
  • Volume
    1
  • fYear
    1997
  • fDate
    1997
  • Abstract
    Ferroresonance phenomena are due to the interaction between nonlinear inductances and capacitances of a power network forming a resonant circuit. These phenomena may be caused by switching operations or such disturbances as temporary short-circuits. They are characterised by the possible existence of several stable states, besides the normal steady-state, that induce dangerous overcurrents and overvoltages. The present study deals with the ferroresonance phenomena in three-phase isolated neutral power networks with three single-phase voltage transformers
  • Keywords
    power system stability; disturbances; nonlinear capacitance; nonlinear inductance; overcurrents; overvoltages; power system ferroresonance phenomena; resonant circuit; single-phase voltage transformers; stability; switching operations; temporary short-circuits; three-phase isolated neutral power networks;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
  • Conference_Location
    Birmingham
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-674-1
  • Type

    conf

  • DOI
    10.1049/cp:19970458
  • Filename
    671638