• DocumentCode
    2956443
  • Title

    Behavior of directional protection from fault to ground with interrupted arc

  • Author

    Shalin, A.I. ; Kondranina, E.A.

  • Author_Institution
    Novosibirsk State Tech. Univ., Novosibirsk
  • fYear
    2007
  • fDate
    3-6 Oct. 2007
  • Firstpage
    348
  • Lastpage
    352
  • Abstract
    Directional current protection from grounding has been widespread in distribution networks and voltage equipment, 6-35 kV. One of the most complicated operational regimes of the protection is fault to ground (FG) accompanied by an interrupted arc. Due to the moments of the arc ignition and arc starvation are random values, not only oscillograms of zero frequency current and voltage get distorted to a great extent, but the angle between the components of industrial and voltage frequencies change randomly. All that has a great influence on the protection´s behavior.
  • Keywords
    arcs (electric); earthing; power distribution protection; arc ignition; arc starvation; directional current protection; fault-to-ground protection; interrupted arc; oscillograms; power distribution networks; voltage 6 kV to 35 kV; voltage equipment; zero frequency current; zero frequency voltage; Circuit faults; Frequency; Grounding; Ignition; Protection; Protective relaying; Pulse measurements; Signal processing; Transformers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Strategic Technology, 2007. IFOST 2007. International Forum on
  • Conference_Location
    Ulaanbaatar
  • Print_ISBN
    978-1-4244-3589-0
  • Electronic_ISBN
    978-1-4244-1831-2
  • Type

    conf

  • DOI
    10.1109/IFOST.2007.4798602
  • Filename
    4798602