• DocumentCode
    2957807
  • Title

    Tests for temperature-rise, power-dissipation measurement and breaking capacity on a prototype model of a high-voltage fuse

  • Author

    Saqib, M.A.

  • Author_Institution
    Fac. of Electron. Eng., GIK Inst. of Eng. Sci. & Technol., Topi, Pakistan
  • fYear
    2003
  • fDate
    8-9 Dec. 2003
  • Firstpage
    476
  • Lastpage
    481
  • Abstract
    This work presents the results for temperature-rise, power-dissipation measurement and breaking-capacity tests on a prototype model during the development of a current-limiting high-voltage fuse. The power-dissipation and temperature-rise measurements are made when rated current was passed through the fuse carrier. The temperature of various parts of the fuse-link has been measured using thermocouples: the results are within the limits set by several international standards. The upper limit of the results obtained by the power-dissipation measurements is around 110 W. The results of successive breaking tests, during the development work, for Test Duty 1 - at 11 kV, 20 kA - show gradual improvements.
  • Keywords
    electric fuses; high-voltage techniques; overcurrent protection; power measurement; standards; switchgear testing; temperature measurement; thermal stresses; breaking-capacity tests; current-limiting high-voltage fuse; fuse carrier; fuse-link temperature; international standards; power-dissipation measurement; prototype model; rated current; temperature-rise tests; test duty; thermocouples; Circuit breakers; Current measurement; Design engineering; Fuses; Power engineering and energy; Power transformer insulation; Prototypes; Temperature measurement; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Multi Topic Conference, 2003. INMIC 2003. 7th International
  • Print_ISBN
    0-7803-8183-1
  • Type

    conf

  • DOI
    10.1109/INMIC.2003.1416774
  • Filename
    1416774