• DocumentCode
    2959079
  • Title

    Evaluation of 400V DC distribution in telco and data centers to improve energy efficiency

  • Author

    Pratt, Annabelle ; Kumar, Pavan ; Aldridge, Tomm V.

  • Author_Institution
    Intel Corp., Hillsboro
  • fYear
    2007
  • fDate
    Sept. 30 2007-Oct. 4 2007
  • Firstpage
    32
  • Lastpage
    39
  • Abstract
    In a typical data center, less than half the energy consumed is delivered to the compute load, with the rest lost in power conversion, distribution and cooling. Traditionally power distribution is at 400/480 V AC in data centers and at -48 V DC in telco facilities. Higher voltage DC has been proposed as an energy efficient distribution option for both types of facilities, and this paper presents an analytical evaluation of several data center power delivery architectures over a range of loads, showing that a 400 V facility-level DC distribution option is the most efficient. The equipment required to support such an architecture is discussed and results from a small scale demonstration are included.
  • Keywords
    power consumption; power distribution; telecommunication power supplies; DC distribution; Telco; data centers; energy efficiency; power conversion; power delivery architectures; voltage -48 V; voltage 400 V; voltage 480 V; Cooling; Costs; Distributed computing; Energy efficiency; Low voltage; Microprocessors; Power conversion; Power distribution; Power supplies; Uninterruptible power systems;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2007. INTELEC 2007. 29th International
  • Conference_Location
    Rome
  • Print_ISBN
    978-1-4244-1627-1
  • Electronic_ISBN
    978-1-4244-1628-8
  • Type

    conf

  • DOI
    10.1109/INTLEC.2007.4448733
  • Filename
    4448733