Title :
Effect of terminal connections on SFRA results of three-winding power transformers
Author :
Murawwi, Esam Al ; Mardiana, Redy ; Su, Qi
Abstract :
This paper presents some case studies on the effects of terminal connections that affect Sweep Frequency Response Analysis (SFRA) results. Wrong or different terminal connections might lead to confusing SFRA results which could be misinterpreted in the assessment of transformer winding conditions. Effect of grounding the tertiary winding, opening the tertiary winding, and connecting the neutral point in the terminal connections are highlighted in this work.
Keywords :
frequency response; power transformers; transformer windings; SFRA result; grounding effect; neutral point; sweep frequency response analysis; terminal connection; three-winding power transformer; Frequency measurement; Grounding; Oil insulation; Power transformers; Transformer cores; Windings;
Conference_Titel :
Electric Power and Energy Conversion Systems (EPECS), 2011 2nd International Conference on
Conference_Location :
Sharjah
Print_ISBN :
978-1-4577-0804-6
DOI :
10.1109/EPECS.2011.6126823