• DocumentCode
    2964330
  • Title

    A frequency domain method for partial discharge location in underground power cables

  • Author

    Mardiana, Redy ; Firdaus, Ahmad Fajar

  • Author_Institution
    Dept. of Electr. Eng., Pet. Inst., Abu Dhabi, United Arab Emirates
  • fYear
    2011
  • fDate
    15-17 Nov. 2011
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    A frequency domain method to determine the location of partial discharges (PD) from one-end of underground power cable is presented in this paper. This method is developed based on the phase difference between the direct and reflected waves of a PD pulse. The phase difference as a function of frequency is obtained using the cross Fourier spectral density function. The defect in the cable can be located after implementing a phase unwrapping algorithm. Laboratory experiments using a model of a 3.3 kV, 50m underground cable have been carried out and the statistical results are presented as well. The comparison results with the time domain methods are also given to demonstrate the effectiveness of the proposed method.
  • Keywords
    Fourier analysis; frequency-domain analysis; partial discharge measurement; power cable insulation; underground cables; PD pulse waves; cross Fourier spectral density function; frequency domain method; partial discharge location determination; phase difference; phase unwrapping algorithm; size 50 m; underground power cables; voltage 3.3 kV; Equations; Frequency domain analysis; Frequency estimation; Mathematical model; Partial discharges; Power cables; Time domain analysis; PD location; cable insulation; partial discharge; phase difference;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power and Energy Conversion Systems (EPECS), 2011 2nd International Conference on
  • Conference_Location
    Sharjah
  • Print_ISBN
    978-1-4577-0804-6
  • Type

    conf

  • DOI
    10.1109/EPECS.2011.6126849
  • Filename
    6126849