Abstract :
A new type of “dual-contact” structure of vacuum interrupter is proposed in the paper. It consists of main contact and arc contact, which are used to carry rated current and break short circuit current, respectively. During the closing/opening of vacuum circuit breaker, arc contact is first closed and post breaking, however, main contact is post closed and first breaking. So there must be the current transfer process. In this paper, during the breaking process of vacuum circuit breaker, a model of current transfer is used in the investigation of current transfer, and the maximum possible current transfer time is obtained. This analysis is helpful to the research of large current vacuum interrupters with dual-contact.
Keywords :
arcs (electric); electrical contacts; short-circuit currents; vacuum interrupters; arc contact; breaking process; current transfer process analysis; dual-contact structure; large current vacuum interrupters; short circuit current; Circuit breakers; Integrated circuit modeling; Interrupters; Resistance; SPICE; Short circuit currents; Springs;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
Conference_Location :
Tomsk
ISSN :
1093-2941
Print_ISBN :
978-1-4673-1263-9
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2012.6412486
Filename :
6412486
Link To Document :
بازگشت