Title : 
Measurement of hydro-generator´s end region temperature
         
        
            Author : 
Bertalanic, Zoran ; Maljkovic, Zlatko ; Pavlica, Milutin
         
        
            Author_Institution : 
Energy Inst. Inc., Zagreb
         
        
        
        
        
        
            Abstract : 
Paper presents results of measurements of hydrogenerator´s end region steady state temperatures. Measurements were carried out in case of two hydro-generators, 65 MVA and 40 MVA respectively, installed in the same power plant. Four thermal probes were placed in each of the generators. Some of the tests, carried out for under-excited load conditions, had to be interrupted because the temperature of the end region exceeded 130degC. Results indicate that end region temperature should be monitored.
         
        
            Keywords : 
hydroelectric generators; temperature measurement; hydro-generator end region temperature; power plant; thermal probes; under-excited load conditions; AC generators; Electric variables measurement; Lamination; Loss measurement; Magnetic flux; Magnetic materials; Power generation; Stator cores; Teeth; Temperature measurement;
         
        
        
        
            Conference_Titel : 
Electrical Machines, 2008. ICEM 2008. 18th International Conference on
         
        
            Conference_Location : 
Vilamoura
         
        
            Print_ISBN : 
978-1-4244-1735-3
         
        
            Electronic_ISBN : 
978-1-4244-1736-0
         
        
        
            DOI : 
10.1109/ICELMACH.2008.4800076