DocumentCode :
2971235
Title :
VCB contact system electrical endurance on-line condition monitoring technology and its application
Author :
He Jia-min ; Fan Xing-ming ; Zhang Xin ; Huang Zhi-chao ; Zou Qi-tao ; Liang Cong ; Shi Wei-jian
Author_Institution :
Dept. of Electr. Eng. & Autom., Guilin Univ. of Electron. & Technol., Guilin, China
fYear :
2012
fDate :
2-7 Sept. 2012
Firstpage :
513
Lastpage :
516
Abstract :
In order to reduce the number of accidents and prevent possible troubles due to the failures of VCBs, one valid way is to monitor their performance and condition on-line. Based on the understanding and development of condition based maintenance (CBM) of high-voltage circuit breakers, the authors give some general introduction to electrical endurance on-line condition monitor for VCBs, in which the stress put on the non-intrusive method and device for determination of the arcing duration. The principle and configuration for arcing duration detect are emphatically expounded in our research, in which the electromagnetic induction theory is adopted for the arcing initialization and duration detect. The simulation and experimental results of the arcing detect device are provided in detail. The accuracy and stability of the arcing detect device have been demonstrated and it can distinguish co-existing arc signals in three-phase of circuit breakers. In the end, an algorithm for the electrical endurance of vacuum circuit breakers on-line condition monitoring system is proposed, which based on TMS320F2812 one type of DSP281X series produced by Texas Instruments semiconductor. The universally accepted approach of accumulative breaking current of high voltage circuit breaker contact to diagnose electrical endurance is used in the High-voltage Circuit Breakers Electrical Endurance On-line Monitor system.
Keywords :
arcs (electric); condition monitoring; electrical contacts; electrical maintenance; vacuum circuit breakers; DSP281X series; TMS320F2812 series; arcing detect device; breaking current; condition based maintenance; high voltage circuit breaker contact; high voltage circuit breakers electrical endurance; on-line condition monitoring system; on-line condition monitoring technology; vacuum circuit breaker contact system; Circuit breakers; Coils; Contacts; Detectors; Educational institutions; Indexes; Monitoring;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
Conference_Location :
Tomsk
ISSN :
1093-2941
Print_ISBN :
978-1-4673-1263-9
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2012.6412568
Filename :
6412568
Link To Document :
بازگشت