• DocumentCode
    2973314
  • Title

    A study on the influence of forest fire on polymer insulators

  • Author

    Lee, Won-Kyo ; Choi, In-Hyuk ; Lee, Dong-Il ; Hwang, Kab-Cheol

  • Author_Institution
    Korea Electr. Power Res. Inst. (KEPRI)
  • fYear
    2008
  • fDate
    6-9 Sept. 2008
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    The forest fire simulation tests were performed with polymer and porcelain insulators at Gochang Power Testing Center. These tests consisted of open flame rising up to 600~820degC as being measured at insulator surface. Mechanical and electrical characteristics such as specific mechanical load, low frequency dry flashover voltage and impulse flashover voltage were analyzed for the polymer insulators before, during and after simulation tests compared with porcelain insulators. At the end of fire simulation tests, there was no detrimental deterioration of any insulators. All insulators passed the criteria of KEPCO specification. This study showed that forest fire simulation had no impact on polymer insulators.
  • Keywords
    fires; flames; flashover; impulse testing; insulator testing; polymer insulators; porcelain insulators; Gochang Power Testing Center; KEPCO specification; forest fire simulation tests; impulse flashover voltage; insulator deterioration; insulator surface; low-frequency dry flashover voltage; mechanical load; open flame; polymer insulators; porcelain insulators; temperature 600 C to 820 C; Dielectrics and electrical insulation; Electric variables; Fires; Flashover; Insulator testing; Performance evaluation; Plastic insulation; Polymers; Porcelain; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines, 2008. ICEM 2008. 18th International Conference on
  • Conference_Location
    Vilamoura
  • Print_ISBN
    978-1-4244-1735-3
  • Electronic_ISBN
    978-1-4244-1736-0
  • Type

    conf

  • DOI
    10.1109/ICELMACH.2008.4800204
  • Filename
    4800204