Title :
Measurement of harmonics in different sectors on 11 kV distribution networks
Author :
Zainal, Zafariq ; Ang, S.P. ; Salam, M.A. ; Weira, Pg Jamra ; Goh, Rick Siow Mong
Author_Institution :
Inst. Teknol. Brunei, Bandar Seri Begawan, Brunei
Abstract :
The power quality issues nowadays subjected to the distribution network is the most concern due to employing power electronics and control equipment in the residential, commercial, industry and a grid connected solar plant. This paper presents the practical measurement at seven different locations of 11 kV distribution network in Brunei Darussalam. From the measurements, it is found that the individual harmonic voltage distortion (%) and total harmonic distortion (%) are below the IEEE 519-1992 standard. In addition, the current and voltage THD (%) of the neutral phase are higher than the IEEE 519-1992 standard.
Keywords :
distribution networks; harmonic distortion; power harmonic filters; power measurement; power supply quality; control equipment; distribution networks; grid connected solar plant; harmonic voltage distortion; harmonics measurement; power electronics; power quality issues; total harmonic distortion; voltage 11 kV; Current measurement; Harmonic analysis; IEEE standards; Industries; Power quality; Power system harmonics; Voltage measurement; current harmonics; distribution network; harmonics; neutral current; power quality monitoring; total harmonic distortion; voltage harmonics;