The power system failure on July 23, 1987 in Tokyo
Author :
Kurita, Atsushi ; Sakurai, Takayasu
Author_Institution :
Tokyo Electr. Power Co. Inc., Tokyo, Japan
fYear :
1988
fDate :
7-9 Dec 1988
Firstpage :
2093
Abstract :
A power system failure occurred at 1:19 p.m. on July 23, 1987, in the service area of the Tokyo Electric Power Company Inc. The unusually hot weather led to concentrated mass consumption of electricity, causing a failure which affected 2.8 million customers in the area. There were three major causes of this failure: the power demand level on that day was unusually high; the rate of demand increase exceeded previous levels; and air conditioners which have characteristics such that a fall in voltage leads to a rise in current are in widespread use in Japan. The failure is analysed and countermeasures to mitigate future power failures are presented
Keywords :
air conditioning; electrical faults; power systems; AD 1987 07 23; Japan; TEPCO; Tokyo Electric Power Company Inc.; air conditioners; countermeasures; high power demand; hot weather; power cut; power system failure; Demand forecasting; Frequency; Power demand; Power engineering and energy; Power generation; Power system dynamics; Power systems; Temperature; Voltage; Weather forecasting;