Determining distance relay Zone-1 reach settings to prevent CCVT transient overreach
Author
Franklin, Gregory A. ; Horton, Randy
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Alabama at Birmingham, Birmingham, AL, USA
fYear
2011
fDate
17-20 March 2011
Firstpage
1
Lastpage
5
Abstract
This paper presents the results of a study on determining Zone-1 reach settings for transmission line distance relays to prevent overreach resulting from coupling capacitor voltage transformer (CCVT) transients. In particular, this study focused on digital distance relays and determining appropriate relay reach settings to account for the effects of CCVT transients during faults for CCVTs with active ferroresonant suppression circuits. The results of the study presented herein are based on EMTP simulations that were validated by actual relay tests.
Keywords
potential transformers; power capacitors; power transformer protection; relay protection; CCVT transient overreach; EMTP simulations; active ferroresonant suppression circuit; coupling capacitor voltage transformer transient; distance relay zone-1 reach setting; transmission line distance relay; Impedance; Load modeling; Loading; Protective relaying; Transient analysis;