    Determining distance relay Zone-1 reach settings to prevent CCVT transient overreach

  • Author

    Franklin, Gregory A. ; Horton, Randy

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Alabama at Birmingham, Birmingham, AL, USA
  • fYear
    2011
  • fDate
    17-20 March 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper presents the results of a study on determining Zone-1 reach settings for transmission line distance relays to prevent overreach resulting from coupling capacitor voltage transformer (CCVT) transients. In particular, this study focused on digital distance relays and determining appropriate relay reach settings to account for the effects of CCVT transients during faults for CCVTs with active ferroresonant suppression circuits. The results of the study presented herein are based on EMTP simulations that were validated by actual relay tests.
  • Keywords
    potential transformers; power capacitors; power transformer protection; relay protection; CCVT transient overreach; EMTP simulations; active ferroresonant suppression circuit; coupling capacitor voltage transformer transient; distance relay zone-1 reach setting; transmission line distance relay; Impedance; Load modeling; Loading; Protective relaying; Transient analysis;