  • Abstract
    This paper reviews the cast coil transformer operating experiences of a large forest products company. The excellent operating record of more than 230 transformers is strong testimony for cast coil insulation systems and for the rating specification used. The temperature versus loading curves that were developed have been very helpful in providing user plant personnel with understanding and acceptance of cast coil transformers. Thanks to some unusual short-term overloading conditions, data were gathered to provide thermal time constant curves.
  • Keywords
    casting; coils; forestry; load (electric); power transformer insulation; thermal analysis; transformer windings; cast coil insulation systems; cast coil transformers; forest products company; operating experiences; rating specification; short-term overloading conditions; thermal time constant curves; user experiences; Coils; Cooling; Detectors; Force control; System testing; Temperature control; Temperature measurement; Temperature sensors; Transformers; Voltage control;