• DocumentCode
    2988536
  • Title

    Electrode erosion under high current vacuum arcs

  • Author

    Ji-yan, Zou ; Li-Chun, Cheng

  • Author_Institution
    Dept. of Electr. Power Eng., Huazhong Univ. of Sci. & Technol., Hubei, China
  • fYear
    1989
  • fDate
    18-20 Sep 1989
  • Firstpage
    253
  • Lastpage
    255
  • Abstract
    Electrode erosion was measured under conditions of practical high current and axial magnetic field (AMF). Arc interruptions were made in a demountable vacuum chamber. Electrode erosion was assessed by weighting. It is shown that the rate of electrode erosion with AMF is 39.8 μg/C and that without AMF it is 1.3 mg/C; the anode gains 15 μg/C for diffused arcs
  • Keywords
    circuit-breaking arcs; magnetic field effects; axial magnetic field; demountable vacuum chamber; high current vacuum arcs; rate of electrode erosion; Anodes; Cathodes; Circuit testing; Current measurement; Electrodes; Magnetic fields; Switches; Vacuum arcs; Vacuum technology; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Contacts, 1989., Proceedings of the Thirty Fifth Meeting of the IEEE Holm Conference on
  • Conference_Location
    Chicago, IL
  • Type

    conf

  • DOI
    10.1109/HOLM.1989.77947
  • Filename
    77947