Abstract
The goal of this project was to evaluate the performance of the operative state of power capacitors installed in the substations of 13.8 -24/34.5 kV and even 138 kV of an electric power company in Rio de Janeiro-Brazil. We intend here to present the developed methodology and to argue about the reached issues. We used the Partial Discharges (PD) measurement technique with the registration of acoustic signals in the ultrasound band. With capacitors tanks under potential, we implemented a special system isolated with an optical fiber. One of the main issues obtained in this work was the development of a simple and easy technique of measurement in the field (using ultrasonic piezoelectric sensors, a digital oscilloscope and a notebook), which made the evaluation of more than 300 capacitive units possible.
Keywords
partial discharge measurement; power capacitors; power distribution; ultrasonic applications; acoustic signals registration; digital oscilloscope; distribution system; operative state; partial discharges measurement; power capacitors; substations; ultrasonic piezoelectric sensors; Acoustic measurements; Acoustic sensors; Capacitive sensors; Measurement techniques; Optical fibers; Partial discharges; Power capacitors; Substations; Ultrasonic imaging; Ultrasonic variables measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2007. CEIDP 2007. Annual Report - Conference on
Conference_Location
Vancouver, BC
Print_ISBN
978-1-4244-1482-6
Electronic_ISBN
978-1-4244-1482-6
Type
conf
DOI
10.1109/CEIDP.2007.4451529
Filename
4451529
Link To Document