DocumentCode
2996901
Title
Experimental investigation on flashover performance of glass insulator for DC transmission lines at high altitudes
Author
Zhang, Fuzeng ; Mao, Yingke ; Wang, Xin ; Wang, Liming ; Guan, Zhicheng ; Wen, Hua ; Li, Ruihai ; Ma, Yi
Author_Institution
Tsinghua Univ., Shenzhen
fYear
2007
fDate
14-17 Oct. 2007
Firstpage
324
Lastpage
328
Abstract
This paper presents the results of an investigation on the DC flashover characteristic of contaminated glass insulators at natural high altitudes (1970 m). The arcing behavior on natural contaminated glass insulator surfaces was studied using a high-speed camera. The experimental results show that the DC arcs have a significant influence on the flashover performance of contaminated glass insulator since the DC arcs levitate more easily from the insulator surfaces at high altitudes than at sea level. The insulator profiles, contamination distribution condition, and suspension patterns (I-and V-strings) have a strong effect on the arc behaviors resulting in an obvious difference for the utilization ratio of leakage distance of the glass insulator, and this has a strong influence on the flashover voltages.
Keywords
DC transmission networks; arcs (electric); cameras; flashover; DC flashover; DC transmission lines; arcing; contamination distribution; glass insulator; high altitudes; high-speed camera; suspension patterns; Circuit testing; Dielectrics and electrical insulation; Flashover; Glass; Insulator testing; Marine pollution; Power transmission lines; Sea surface; Transmission lines; Voltage; Arc; Flashover characteristic; Glass insulator; Leakage distance;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2007. CEIDP 2007. Annual Report - Conference on
Conference_Location
Vancouver, BC
Print_ISBN
978-1-4244-1482-6
Electronic_ISBN
978-1-4244-1482-6
Type
conf
DOI
10.1109/CEIDP.2007.4451567
Filename
4451567
Link To Document