• DocumentCode
    3003196
  • Title

    A methodology to evaluate harmonic penetration in power networks

  • Author

    Lu, Jianfeng ; Li, Gengyin ; Zhou, Ming ; Lo, K.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Univ. of Strathclyde, Glasgow, UK
  • fYear
    2011
  • fDate
    17-19 Oct. 2011
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The paper presents an iterative process to calculate the voltage magnitudes and phase angles at each bus in a power network for each harmonic frequency (include fundamental frequency). The method indicated in the paper is based on Newton-Raphson method. A six-pulse line commutated converter and a twelve-pulse phase control delta-star connected converter are studied. They are regarded as harmonic sources in the paper. The algorithm is illustrated by taken a five-bus-five-line model.
  • Keywords
    Newton-Raphson method; power conversion harmonics; Newton-Raphson method; five-bus-five-line model; harmonic frequency; harmonic penetration evaluation; harmonic sources; iterative process; phase angles; power networks; six-pulse line commutated converter; twelve-pulse phase control delta-star connected converter; voltage magnitudes; Equations; Harmonic analysis; Mathematical model; Phase control; Power system harmonics; Reactive power; Converter; Harmnoic Penetration; Harmonic; Power Network;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Power Quality and Utilisation (EPQU), 2011 11th International Conference on
  • Conference_Location
    Lisbon
  • ISSN
    2150-6647
  • Print_ISBN
    978-1-4673-0379-8
  • Type

    conf

  • DOI
    10.1109/EPQU.2011.6128955
  • Filename
    6128955