DocumentCode :
3004426
Title :
An Optimized 5 kW, 147 W/in3 Telecom Phase-Shift DC-DC Converter with Magnetically Integrated Current Doubler
Author :
Badstuebner, U. ; Biela, J. ; Faessler, B. ; Hoesli, D. ; Kolar, J.W.
Author_Institution :
Power Electron. Syst. Lab., ETH Zurich, Zurich
fYear :
2009
fDate :
15-19 Feb. 2009
Firstpage :
21
Lastpage :
27
Abstract :
In the last decade there has been a tremendous growth in the number of data centers due to the increasing demand for Internet services. At the same time, the cost for energy and materials have increased because of reducing resources and increased demand. That has caused a change in the driving forces for new power supply development, with more consideration on power density and efficiency. The commonly used DC-DC converter in the power supply unit (PSU) for data centers and telecom applications are full bridge phase-shift converters since they meet the demands of high power levels and concurrently efficient power conversion as well as a compact design. The constant operating frequency allows a simple control and EMI design. To develop a new converter with higher power density and/or high efficiency the designer has a lot of degrees of freedom. An optimization procedure, based on comprehensive analytical models, has been developed and leads to the optimal parameters (e.g. switching frequency or transformer design) to achieve the most compact and/or efficient design. In this paper an volume optimized 400 V/48 V phase-shift DC-DC converter with current doubler rectifier based on analytical models is constructed. The power density of the converter is increased by integrating the output inductors in the transformers core. The intrinsic voltage ringing of the rectifier diodes is damped by a lossless magnetic snubber, which feeds ringing energy to the output. Experimental results prove the theoretical analytical models and the design procedure.
Keywords :
DC-DC power convertors; Internet; computer centres; electromagnetic interference; rectifiers; snubbers; EMI design; Internet services; current doubler rectifier; data centers; lossless magnetic snubber; magnetically integrated current doubler; output inductors; phase-shift DC-DC converter; power 5 kW; power density; power efficiency; power supply; rectifier diodes; transformers core; Analytical models; Bridge circuits; Costs; DC-DC power converters; Frequency; Power conversion; Power supplies; Rectifiers; Telecommunications; Web and internet services;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied Power Electronics Conference and Exposition, 2009. APEC 2009. Twenty-Fourth Annual IEEE
Conference_Location :
Washington, DC
ISSN :
1048-2334
Print_ISBN :
978-1-4244-2811-3
Electronic_ISBN :
1048-2334
Type :
conf
DOI :
10.1109/APEC.2009.4802627
Filename :
4802627
Link To Document :
بازگشت