Abstract :
When an EHV transmission line is energized by the closing of a circuit breaker, there are a number of well known parameters which effect the transient overvoltages on the line. These include the impact of pole closing span, use of closing resistors and point-on-wave closing. These factors are investigated along with the little studied effect of contact closing pre-strike included. Probability distribution of overvoltages for transmission line energizations are the means for comparing the various effects
Keywords :
circuit breakers; overvoltage; power system transients; power transmission lines; probability; EHV transmission line energisation; breaker pre-strike; circuit breaker closing; closing resistors; point-on-wave closing; pole closing span; probability distribution; switching surges; transient overvoltages; Circuit breakers; Circuit testing; Distributed parameter circuits; Power system transients; Probability distribution; Resistors; Surges; System testing; Transmission lines; Voltage;