DocumentCode
3008149
Title
Induced voltage on objects under six-phase transmission line
Author
Sidik, M.A.B. ; Ahmad, Harith ; Malek, Zulkurnain Abd ; Buntat, Zolkafle ; Bashir, Nouruddeen ; Zarin, M.I.A. ; Nawawi, Z. ; Jambak, M.I.
Author_Institution
Inst. of High Voltage & High Current, Univ. Teknol. Malaysia, Skudai, Malaysia
fYear
2011
fDate
21-24 Nov. 2011
Firstpage
968
Lastpage
970
Abstract
This paper presents results of an experimental investigation on voltage induced on objects under a six-phase transmission line due to line switching incidences. In this work, the voltage induced on a vertical receiver and a pipeline due to line energization and de-energization in a six-phase power transmission line system is reported. The research was carried out using a six-phase transmission line mock-up system with ratio of 5/132 kV. The results showed that the induced voltage on the objects is less than 4 kV. In addition the high induced voltage experienced by the vertical receiver was from the left side of the phase composition while the pipeline experienced higher induced voltage from the right side phase composition.
Keywords
power transmission lines; induced voltage; line deenergization; line energization; line switching incidences; pipeline; six-phase power transmission line; six-phase transmission line mock-up system; vertical receiver; Pipelines; Power transmission lines; Probes; Receivers; Surges; Switches; Transmission line measurements; induced voltage; six-phase system; surge; switching; transmission line;
fLanguage
English
Publisher
ieee
Conference_Titel
TENCON 2011 - 2011 IEEE Region 10 Conference
Conference_Location
Bali
ISSN
2159-3442
Print_ISBN
978-1-4577-0256-3
Type
conf
DOI
10.1109/TENCON.2011.6129254
Filename
6129254
Link To Document