  • Abstract
    The electric field distributions for HVDC wall bushings with different dry zone lengths are discussed and their critical flashover voltages predicted using an E-field based model. The simulation yields results in good agreement with experimental results. It is shown that some important aspects of wall bushing flashover, such as the U-shaped characteristics of critical flashover voltage versus dry zone length, critical dry zone length, are well reproduced by the simulation
  • Keywords
    HVDC power transmission; bushings; electric fields; flashover; simulation; E-field based model; HVDC wall bushing performance; U-shaped characteristics; critical dry zone length; critical flashover voltage; critical flashover voltages prediction; dry zone lengths; electric field distributions; unevenly wetted conditions; Circuit simulation; Computational modeling; DC-DC power converters; Equivalent circuits; Flashover; HVDC transmission; Insulators; Predictive models; Surface discharges; Voltage;