Title :
Reactive power and unbalance compensation with DSTATCOM
Author :
XiangQian, Tong ; Keqing, Xi ; Ming, Shen ; Xianhong, Ma
Author_Institution :
Sch. of Autom. & Inf. Eng., Xi´´an Univ. of Technol.
Abstract :
Load unbalance is a general phenomenon in low-voltage three-phase distribution system. As the negative sequence voltage will cause abnormal operation of electric equipments and decrease the power quality, a low-voltage distribution static synchronous compensator (DSTATCOM) is proposed to compensate both the reactive power and load unbalance caused by asymmetric loads in a three-phase power system, and an asymmetric control method based on symmetrical component transformation and d-q transformation for the DSTATCOM is presented. An experiment system of a low-voltage DSTATCOM was developed, and the generation method of SPWM pulse was implemented. The results of experiments, which conducted with balanced load and unbalanced load, verify the validity of compensation algorithm, and also show that the SPWM-based DSTATCOM can compensate reactive power and load unbalance synchronously
Keywords :
PWM invertors; power distribution control; reactive power; static VAr compensators; DSTATCOM; SPWM; asymmetric control; d-q transformation; distribution static synchronous compensator; distribution system; electric equipment; load unbalance compensation; power quality; reactive power compensation; symmetrical component transformation; three-phase power system; voltage source inverter; Control systems; Energy loss; Inductors; Power quality; Pulse power systems; Pulse width modulation; Reactive power; Reactive power control; Space vector pulse width modulation; Voltage control; DSTATCOM; reactive power; unbalanced load;
Conference_Titel :
Electrical Machines and Systems, 2005. ICEMS 2005. Proceedings of the Eighth International Conference on
Conference_Location :
Nanjing
Print_ISBN :
7-5062-7407-8
DOI :
10.1109/ICEMS.2005.202733