Abstract
In this paper, we analyzed the characteristics of PD (Partial Discharge) that occurred in the S-LBS(Solid insulated Load Break Switchgear). The PD pulses generated by void, floating and vacuum leakage were measured by IEC60270 method. The PDIV(Partial Discharge Inception Voltage), phase, pulse magnitude and PD pattern were used for analysis and classification.
Keywords
partial discharges; switchgear insulation; IEC60270 method; PDIV; S-LBS; floating leakage; partial discharge characteristics; partial discharge inception voltage; partial discharge pulse; pulse magnitude; solid insulated load break switchgear; vacuum leakage; void; Assembly; Discharges (electric); Electric fields; Materials; Partial discharges; Switchgear; Voltage measurement; floating; partial dischrget; pd pattern; slbs; vacuum interrupter; void;