    Analysis of UHF PD monitoring data by means of normalized cross-correlation

  • Author

    Beltle, M. ; Muller, A. ; Tenbohlen, Stefan

  • Author_Institution
    Inst. of Power Transm. & High Voltage Technol., Univ. of Stuttgart, Stuttgart, Germany
  • fYear
    2012
  • fDate
    23-27 Sept. 2012
  • Firstpage
    103
  • Lastpage
    106
  • Abstract
    The paper presents a long-term monitoring example of an aged generator step-up transformer with several PD sources showing different activity. Monitoring data is recorded by the use of the electromagnetic PD measurement method, also known as the UHF-method. The phase resolved PD patterns of collected UHF measuring data are analyzed using cross-correlation. The method searches for characteristics of a typical pattern called template. PRPD patterns of the entire dataset are evaluated. The result is the time dependent occurrence of a specific pattern, respectively a specific PD source.
  • Keywords
    partial discharges; power transformers; PD sources; PRPD patterns; UHF PD monitoring data analysis; UHF measuring data; UHF-method; aged generator step-up transformer; cross-correlation; data monitoring; electromagnetic PD measurement method; long-term monitoring example; normalized cross-correlation; Correlation; Correlation coefficient; Monitoring; Oil insulation; Partial discharges; Power transformers; UHF measurements; cross-correlation; long-term UHF measurement; monitoring; partical discharge; phase resolved patterns;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
  • Conference_Location
    Bali
  • Print_ISBN
    978-1-4673-1019-2
  • Type

    conf

  • DOI
    10.1109/CMD.2012.6416321
  • Filename
    6416321