DocumentCode :
3011685
Title :
Induced voltage analysis with adjacent phases of the three-limb and five-limb trasnformers
Author :
Jong-Man Joung ; Chul-bae Park ; Han-hong Kim ; Dong-yeol Shin ; Dong-Myung Kim
Author_Institution :
Facility Diagnosis Center of Korea Electr. Power Cooperation (KEPCO), Daejeon, South Korea
fYear :
2012
fDate :
23-27 Sept. 2012
Firstpage :
1029
Lastpage :
1031
Abstract :
Voltage at the interrupted windings that was induced with adjacent two phases of the windings was analyzed. There are three-limb and five-limb core type of three phase transformers typically. MOF is one of the three-limb transformers and power transformer is five-limb type in KEPCO distribution systems. In the three-limb transformers 100% of the rated voltages were induced and the load that connected outage phase could be supplied with two sound different phases so the transformers could be overloaded. The over loading failure case was presented. In the five-limb transformers the induced voltages were about 80% of the rated voltage at no-load condition but the load power couldn´t be supplied because of the outer limb that makes leakage flux linking phase to phase windings. The induced voltages depend on the core types but the voltage rate of primary and secondary at the outage windings is constant. The windings condition can be checked by the voltage ratio.
Keywords :
power distribution protection; power transformers; transformer windings; KEPCO distribution systems; MOF; adjacent phases; connected outage phase; core types; induced voltage analysis; interrupted windings; leakage flux linking phase-to-phase windings; loading failure case; no-load condition; outage winding condition; outer limb; power transformer; three-limb five-limb transformer; transformers phases; voltage rate; voltage ratio; winding analysis; Magnetic flux; Phase transformers; Power transformers; Transformer cores; Voltage transformers; Windings; MOF; core type; five-limb; shell type; three-limb; transformers;
fLanguage :
English
Publisher :
ieee