DocumentCode
3012196
Title
Development of remaining life estimation for MV PILC due to electrical stress using statistical method
Author
Zarim, Z.A.A. ; Anthony, T.M.
Author_Institution
HV Cable Diagnostics, Kajang, Malaysia
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
1151
Lastpage
1155
Abstract
In Malaysia, PILC cable has been used for more than 25 years. Based on the cable manufacturers´ recommendation, the chronological lifetime of PILC is 40 years. However, the physical age of the cable may be lower due to various stresses experienced by the cables. Since there are 41,911 km of PILC cables in the system (more than 50% population), there must be a strategy to prioritize the replacement of PILC cables. Therefore the aim of this study is to determine the remaining life of the existing PILC in Malaysia. Based on the literature review, a well-known method to estimate remaining life is to use Accelerated Life Testing (ALT). ALT is a method used in this project to accelerate the aging of the samples to fail faster than normal aging. The data collected from the ALT are analyzed using Weibull Distribution and Inverse Power Law formula to predict remaining life of the PILC cables.
Keywords
Weibull distribution; paper; power cable insulation; remaining life assessment; statistical analysis; ALT; MV PILC cable; Malaysia; Weibull distribution; accelerated life testing; electrical stress; inverse power law formula; remaining life estimation; statistical method; Cable insulation; Electric breakdown; Life estimation; Moisture; Power cables; Stress; Temperature measurement; Acceleated Life Testing; PILC; remaining life;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location
Bali
Print_ISBN
978-1-4673-1019-2
Type
conf
DOI
10.1109/CMD.2012.6416363
Filename
6416363
Link To Document