This article describes a new on-line method for capacitance and dissipation factor measurements of high voltage bushings, for recording grid transients and for partial discharge monitoring at power transformers. Failure statistics identify HV bushings as one of the major reasons for transformer failures, which motivates operators for continuous on-line monitoring of their insulation systems health. The needed accuracy for reliable detection of failures is in the range of 5 pF for capacitance and 0.1 % for dissipation factor. For reaching this goal, a relative comparison of the bushing currents of the three phases, measured at the bushing taps, does not provide sufficient accuracy due to imbalances in the network. Additionally, simultaneous ageing, as it can be anticipated for a three phase transformer, will not be detected. To overcome these shortcomings, this paper introduces an absolute method for measuring capacitance and dissipation factor of HV bushings. Even under field conditions a measurement accuracy similar to accurate off-line power factor tests was reached. Partial discharges are an early breakdown indicator for HV dielectrics. With the measurement on the HV bushing tap, not only failure of the bushings dielectric but also of the transformer insulation system can be detected. As for off-line measurements, the discrimination between noise and true internal discharges is the key for successful diagnosis. Strategies for sensitive partial discharge measurements under disturbed on-line conditions are described, also involving measurements in the UHF range.
Keywords :
bushings; condition monitoring; partial discharges; power factor; power transformer insulation; HV bushing tap; UHF; bushing currents; capacitance factor measurements; continuous online monitoring; dissipation factor measurements; field conditions; grid transients; insulation systems health; internal discharges; off-line power factor tests; online conditions; online method; partial discharge measurements; partial discharge monitoring; power transformers; three phase transformer; transformer insulation system; Condition monitoring; Conferences; Decision support systems; UHF; bushings; capacitance; dissipation factor; on-line monitoring; partial dischcarges; power transformers;
Conference_Titel :
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location :
Bali
Print_ISBN :
978-1-4673-1019-2
DOI :
10.1109/CMD.2012.6416378