DocumentCode
3013495
Title
Usability of vibration measurement for power transformer diagnosis and monitoring
Author
Beltle, M. ; Tenbohlen, Stefan
Author_Institution
Inst. of Power Transm. & High Voltage Technol., Univ. of Stuttgart, Stuttgart, Germany
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
281
Lastpage
284
Abstract
This paper discusses the use of vibrations for power transformer surveillance. Therefore, basic research of transformer vibration is presented including the physical background of vibrations and methods of measurement in terms of sensor techniques comparing in-oil and outside tank wall measurement. A case study of an outside tank wall measurement performed on an aged generator step-up transformer presents first experiences in terms of long term measurement evaluating data of a 2-years period. A use case for vibration measurement is drawn for direct current (DC) detection in power transformers. DC can couple into 3 phase AC systems from nearby HVDC systems. The core´s subsequent static magnetic field leads to increased core power losses and higher stress for the entire transformer.
Keywords
HVDC power transmission; power transformers; vibration measurement; DC detection; HVDC systems; aged generator step-up transformer; core power losses; direct current detection; power transformer diagnosis; power transformer monitoring; power transformer surveillance; sensor techniques; static magnetic field; tank wall measurement; three-phase AC systems; transformer vibration; vibration measurement; Harmonic analysis; Magnetic cores; Magnetostriction; Oil insulation; Power transformers; Vibration measurement; Vibrations; Diagnosis; HVDC; Monitoring; power Transformers Vibration Analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location
Bali
Print_ISBN
978-1-4673-1019-2
Type
conf
DOI
10.1109/CMD.2012.6416431
Filename
6416431