• DocumentCode
    3016798
  • Title

    Supercritical Boiler Tube Wall Temperature Test Base on the Power Plant Control System Database

  • Author

    Yanzhi, Yu ; Liangbo, Zhang ; Haichuan, Xu ; Duogang, Chen ; Gongjun, Dong ; Bo, Shen ; Sheng, Liu

  • Author_Institution
    Sch. of Power & Mech. Eng., Wuhan Univ., Wuhan, China
  • fYear
    2010
  • fDate
    25-27 June 2010
  • Firstpage
    2193
  • Lastpage
    2196
  • Abstract
    In order to precisely learn the working condition of 600MW supercritical boiler, new temperature measuring points are set on the super-heater tube wall inner the flue. Since the working condition of 600MW supercritical boiler is quite severe, the temperature measuring points can only be used for short-term test. The data acquisition can be carried out automatically and a data storage system is required. The system is composed of measuring points, (thermocouple), data acquisition panel (A/D card), the data servers, industrial computer and other auxiliaries. The testing method in this paper integrates the database of the thermal power control system, by using the existing control system. The signals are directly sent to the redundant channel of the power plant control system. This method only requires new measuring points (thermocouple). The test data can be loaded directly from the SIS database, which saves not only money but also the work.
  • Keywords
    boilers; control engineering computing; data acquisition; database management systems; power plants; thermal power stations; thermocouples; data acquisition panel; data servers; data storage system; industrial computer; power plant control system database; supercritical boiler tube wall temperature test base; temperature measuring points; thermal power control system; thermocouple; Boilers; Databases; Electron tubes; Power generation; Temperature measurement; Testing; database; super-heater; supercritical boiler; temperature test;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Control Engineering (ICECE), 2010 International Conference on
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-6880-5
  • Type

    conf

  • DOI
    10.1109/iCECE.2010.540
  • Filename
    5631769