Abstract :
The application of superconducting fault current limiters in transmission systems is very attractive because the devices offer superior technical performance in comparison to conventional methods to limit fault currents. The superconducting fault current limiters show high impedance during fault period and negligible impedance in the circuit during normal operating conditions. This paper illustrates the operation performance of the active saturated iron-core superconductive fault current limiter (SISFCL) and its current-limiting effect on a transmission system. Moreover, investigations are carried out to explore the impact of the active SISFCL on the distance protection of the transmission line. Novel principle and application solutions are first proposed to eliminate the adverse effects that the active SISFCL has on the distance relay protection. A 500-kV double-circuit transmission system with active SISFCLs is simulated by using the Electromagnetic Transients Program including DC software package. Results from simulation tests have demonstrated the correctness and validity of theoretical analyses.
Keywords :
power transmission protection; relay protection; superconducting fault current limiters; DC software package; active SISFCL; active saturated iron-core superconductive fault current limiter; current-limiting effect; distance relay protection; electric transmission system; electromagnetic transients program; line distance protection; transmission line distance protection; Circuit faults; Current measurement; Fault currents; Impedance; Impedance measurement; Power transmission lines; Transmission line measurements; Current-limiting characteristic; Distance protection; Superconducting fault current limiter; Transmission line; distance protection; superconducting fault current limiter (SFCL); transmission line;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/TASC.2014.2368131
Filename :
6949111
Link To Document :
بازگشت