• DocumentCode
    3030803
  • Title

    Analysis and countermeasure on abnormal operation of one 110kV intelligent substation merging unit

  • Author

    Ji Jianfei ; Wang Lihui ; Yuan Yubo ; Gao Lei

  • Author_Institution
    Jiangsu Electr. Power Res. Inst. Co., Ltd., Nanjing, China
  • fYear
    2013
  • fDate
    20-22 Dec. 2013
  • Firstpage
    3509
  • Lastpage
    3515
  • Abstract
    With the increase of voltage level and more and more secondary devices are located in field, the secondary circuit of substation is in a strong electromagnetic environment. Because the secondary circuit is affected by the interference of switch operations, there are many trip accidents happened in substations without any fault in recently years, which constitutes a serious threat to the power network and harms the safe operation of the electric power system. It is of great theoretical significance and practical value to study the Electro Magnetic Compatibility problem of the transformer substations substation secondary circuit. In this paper, the abnormal phenomenon of one 110kV intelligent substation merging unit is described. And the reason of the abnormal phenomenon is analyzed. Firstly, the EMC experiments specified by the IEC61000-4 standard are carried out. Furthermore, to verify the anti-interference performance of the merging unit, the Electro Magnetic Compatibility experiments above the standard are carried out. The structure of merging unit is improved until the merging unit operates normally. Secondly, to quantitatively analyze the disturbance strength, the electromagnetic disturbance signal is recorded, and the characteristics of amplitude and time-frequency of the recorded signal are analyzed. Finally, this paper puts forward some suggestions about improving the Electro Magnetic Compatibility performance of merging unit.
  • Keywords
    IEC standards; electromagnetic compatibility; power system faults; substation automation; EMC experiments; IEC61000-4 standard; abnormal phenomenon; anti-interference performance; disturbance strength; electromagnetic compatibility experiments; electromagnetic disturbance signal; intelligent substation merging unit; voltage 110 kV; Current transformers; Data acquisition; Interference; Merging; Substations; Switches; Wires; electromagnetic transient disturbance; field installation; intellgient substation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Mechatronic Sciences, Electric Engineering and Computer (MEC), Proceedings 2013 International Conference on
  • Conference_Location
    Shengyang
  • Print_ISBN
    978-1-4799-2564-3
  • Type

    conf

  • DOI
    10.1109/MEC.2013.6885614
  • Filename
    6885614