    A new method for pre-contamination and testing of nonceramic insulators

  • Author

    Karady, George G. ; Rayappa, A. Vincent ; Muralidhar, Mukund ; Ruff, Don L.

  • Author_Institution
    Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ, USA
  • Volume
    1
  • fYear
    1996
  • fDate
    16-19 Jun 1996
  • Firstpage
    263
  • Abstract
    A new method is described in this paper for artificial pollution testing of nonceramic insulators. The pollution was repeated a number of times at three different equivalent salt deposit density (ESDD) levels to check for repeatability. Flashover tests were done using the “withstand” voltage method. The leakage current at both low voltage and high voltage were recorded. High voltage resistance was calculated which was found to be a better predictor of flashover voltage. The results of flashover tests were compared to the slurry method. The flashover voltages obtained by the two methods were found to be similar
  • Keywords
    electric breakdown; flashover; insulator contamination; insulator testing; leakage currents; artificial pollution testing; equivalent salt deposit density; flashover voltages; high-voltage resistance; insulation breakdown tests; leakage current; nonceramic insulators; pre-contamination method; repeatability; slurry method; withstand voltage method; Ceramics; Environmentally friendly manufacturing techniques; Flashover; Industrial pollution; Insulation; Insulator testing; Plastic products; Spraying; Surface contamination; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
  • Conference_Location
    Montreal, Que.
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-3531-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1996.549332
  • Filename
    549332