• DocumentCode
    3043555
  • Title

    Measurement of touch voltage in electrical installations, in TN system, in low voltage earth fault

  • Author

    Corvino, A. ; Maurella, A.

  • Author_Institution
    CEI-Comituto Elettrotecnico Italiano, Milano, Italy
  • Volume
    3
  • fYear
    1996
  • fDate
    13-16 May 1996
  • Firstpage
    1375
  • Abstract
    This paper explains two new methods for the measurement of touch voltage, in TN power systems, under low voltage earth faults. After some general considerations of standard measurements, as a consequence of direct experiences and tests, two new methods (voltage drop and volt-amperometric) have been studied as an alternative to the method which foresees the measurement of fault loop impedance Zs for the direct measurement of touch voltage Uc
  • Keywords
    electric shocks; electrical faults; power system measurement; voltage measurement; TN power system; direct measurement; electric shock protection; low voltage earth fault; standard measurements; touch voltage measurement; volt-amperometric method; voltage drop method; Earth; Electric variables measurement; Impedance measurement; Low voltage; Measurement standards; Power measurement; Power system faults; Power system measurements; Testing; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrotechnical Conference, 1996. MELECON '96., 8th Mediterranean
  • Conference_Location
    Bari
  • Print_ISBN
    0-7803-3109-5
  • Type

    conf

  • DOI
    10.1109/MELCON.1996.551203
  • Filename
    551203