• DocumentCode
    30452
  • Title

    Investigation on Voltage Sags Caused by DG Anti-Islanding Protection

  • Author

    Trindade, Fernanda C. L. ; do Nascimento, Klaus V. ; Vieira, Jose Carlos

  • Author_Institution
    Department of Electrical Energy Systems, University of Campinas (UNICAMP), Brazil
  • Volume
    28
  • Issue
    2
  • fYear
    2013
  • fDate
    Apr-13
  • Firstpage
    972
  • Lastpage
    980
  • Abstract
    This paper investigates the voltage sag caused by distributed generation anti-islanding protection. This is a new power-quality concern associated with distributed generation expansion. Anti-islanding protection aims to disconnect distributed generators immediately after the opening of a recloser. As a consequence, after the reclosing operation, voltage sag will occur in some parts of the distribution system, since the loads are energized immediately but the generators are no longer present. In this context, this work presents the findings on our investigations about this problem. The results show that the resulting voltage sag level can violate power-quality limits. Thus, a set of indices has been introduced to characterize the severity of the voltage sag, and a load flow-based method has been proposed to predict the phenomenon. Sensitivity studies are also conducted in order to identify some key factors that influence this type of voltage depression.
  • Keywords
    Delay effects; Generators; Indexes; Power quality; Regulators; Voltage control; Voltage fluctuations; Anti-islanding protection; distributed generation; power quality (PQ); voltage sag;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2012.2237419
  • Filename
    6420998