• DocumentCode
    3046533
  • Title

    SIMTC: Current transformer model

  • Author

    Sánchez, J.A. ; González, J.W.

  • Author_Institution
    HMV Consulting, Medellin, Colombia
  • fYear
    2010
  • fDate
    15-17 Sept. 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The current transformer model developed is based on the proposal made by "Power System Relaying Committee (PSRC)", the IEC 60044-1 and 60044-6 standards and other technical documents. Therefore, this model proposes to combine the strengths of the PSRC model and IEC standards to verify, select, and validate current transformers used in power systems as the primary element that will deliver information to protection relays. EMTP/ATP was used as simulation platform through its ability to create programming blocks (Models function) and use TACS functions. With the digital model, it is possible to capture information of power system and deliver the results to analyze waveforms at the output of a current transformer. It is also possible to verify important sensitivities which are shown in the last part of the document.
  • Keywords
    IEC standards; current transformers; IEC standards; PSRC model; SIMTC; analyze waveforms; current transformer model; power system relaying committee; programming blocks; Inductance; Magnetization; Permeability; Short circuit currents; Accuracy limit factor (ALF); Current transformer (CT); DC component; Magnetic flux; Saturation core;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    ANDESCON, 2010 IEEE
  • Conference_Location
    Bogota
  • Print_ISBN
    978-1-4244-6740-2
  • Type

    conf

  • DOI
    10.1109/ANDESCON.2010.5633432
  • Filename
    5633432