Abstract :
STATCOM utilization to compensate the reactive power of the grid must be protected from faults in the switches. The switching of the STATCOM makes it more vulnerable to switch failures such as open circuit and short circuit due to high frequency switching. This paper introduces several switching techniques applied to a 13-level cascaded H-bridge inverter topology with fault detection and mitigation. The performance and analysis is evaluated with dynamic fault conditions. Reconfiguring the switch failures in any of the H-bridge by bypassing the faulty H-bridge with a bi-directional switch, along with THD spectrum analysis is presented with graphical representation.
Keywords :
invertors; static VAr compensators; 13-level cascaded H-bridge inverter topology; THD spectrum analysis; bidirectional switch; cascaded H-bridge 13 level STATCOM; fault detection; fault mitigation; performance analysis; switch failures; switch fault; Automatic voltage control; Capacitors; Circuit faults; Pulse width modulation; Reactive power; Switches; Switching circuits; Cascaded H-bridge (Hybrid bridge); STATCOM (Static Synchronous Compensator); THD (Total Harminic Distortion);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Instrumentation and Control (ICIC), 2015 International Conference on
Conference_Location :
Pune
Type :
conf
DOI :
10.1109/IIC.2015.7150800
Filename :
7150800
Link To Document :
بازگشت