DocumentCode :
3049541
Title :
Determination of network harmonic impedances using steady-state measurements
Author :
Zhang, Xiqin ; Ahmed, Emad ; Xu, Wilsun
Author_Institution :
Dept. of Electr. Eng., Alberta Univ., Edmonton, Alta., Canada
Volume :
1
fYear :
1999
fDate :
18-22 Jul 1999
Firstpage :
390
Abstract :
This paper presents a simple technique to determine network harmonic impedances. The technique relies on the pre- and post-disturbance steady-state waveforms recorded for naturally-occurring or artificially-introduced disturbances. It makes use of the harmonic excitations existed in the network. Since only steady-state waveforms are needed, the technique can be easily implemented using regular power quality meters. Simulation studies and field measurements are used to demonstrate the usefulness of the proposed method. One of the applications of this technique is to determine the existence of resonance conditions for shunt capacitor applications
Keywords :
electric impedance measurement; harmonic distortion; power supply quality; power system faults; power system harmonics; power system measurement; network harmonic impedances; post-disturbance steady-state waveforms; power quality meters; power system disturbances; pre-disturbance steady-state waveforms; resonance conditions; shunt capacitor applications; steady-state measurements; Capacitors; Data mining; Frequency estimation; Frequency response; Impedance measurement; Power harmonic filters; Power quality; Resonance; Steady-state; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 1999. IEEE
Conference_Location :
Edmonton, Alta.
Print_ISBN :
0-7803-5569-5
Type :
conf
DOI :
10.1109/PESS.1999.784380
Filename :
784380
Link To Document :
بازگشت