Abstract :
In this paper, high voltage, which was raised step by step, was taken on an oil wedge model. Partial discharge (PD) signal was measured by normal IEC 60270 method. And the carbon trace on the pressboard was checked. Using Weibull function, the changes on the type of the PDs, were analyzed. Furthermore, the relationship between the carbon trace and the change of PDs was though about. From the results of the experiments, the PDs changed their type during the high voltage increasing. At the beginning, the PDs were small and produced dim carbon trace. This situation kept on for a long time and the carbon trace gradually extended its range and depth. Then, new type of PDs with very big amplitude appeared just before the breakdown, which we believed produced the breakdown point and due to the breakdown.
Keywords :
IEC standards; Weibull distribution; carbon; partial discharge measurement; power transformer insulation; C; IEC 60270 method; Weibull function; carbon trace; oil wedge model; oil-impregnated paper insulation; partial discharge signal; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Oil insulation; Partial discharges; Petroleum; Power transformer insulation; Power transformers; Surface discharges; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2009. CEIDP '09. IEEE Conference on
Conference_Location :
Virginia Beach, VA
ISSN :
0084-9162
Print_ISBN :
978-1-4244-4557-8
Electronic_ISBN :
0084-9162
Type :
conf
DOI :
10.1109/CEIDP.2009.5377710
Filename :
5377710
Link To Document :
بازگشت